Product Parameters
|
Frame (AF) |
50AF |
|||||
|
Type |
N Type |
|||||
|
Pole (P) |
2-pole |
ABN52C |
||||
|
3-pole |
ABN53C |
|||||
|
4-pole |
ABN54C |
|||||
|
Rated current in A |
15,20,30,40,50 |
|||||
|
Rated operational voltage, Ue |
AC |
(V) |
690 |
|||
|
DC |
(V) |
500 |
||||
|
Rated insulation voltage, Ui |
750 |
|||||
|
Rated impulse withstand voltage Uimp |
8 |
|||||
|
Rated short-circuit breaking capacity(Icu)Ka,iec 60947-2 |
||||||
|
AC |
690V |
2.5 |
||||
|
480/500V |
7.5 |
|||||
|
415/460V |
14 |
|||||
|
380V |
18 |
|||||
|
220/250V |
30 |
|||||
|
DC |
500V(3P) |
5 |
||||
|
250(2P) |
5 |
|||||
|
Ics=% x Icu |
100 |
|||||
|
Dimensions(mm) |
W * H*D |
75*130*60mm |
||||